Permit: T17CM04427

Parcel: 134031170


Addresses:

8878 E ABRAMS LP

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
09/25/2017 FRAMING Approved IVRS - Inspection :*
09/20/2017 FRAMING Denied Anchore bolts are loose, have been cut and dust has not been removed.
All opennings nin electrical boxes shall be sealed; main panel, exterior outlets require romex connector. NEC 300.21
Expose UFER

Support flex ducts

Refee warning


*
09/18/2017 FRAMING Not ready for Inspection complete all noted corrections
09/14/2017 FRAMING Denied dwv and shower pans are not under test. Repair top plates at plumbing pipes on exterior walls. Seal floor penetrations and hole in electrical panel. Tighten loose anchor bolts, correct torn ducts, isolate pex from gang nailers, provide freeze protection in any uninsulated areas. Install romex connector in exterior recepticle box. Locate SDs 3 feet from air vents. Ufer?