Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T17CM04415

Parcel: 129022210


Addresses:

2901 E DEVON ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/21/2017 ELECTRIC - SERVICE UPGRADE Approved
06/20/2017 ELECTRIC - SERVICE UPGRADE Not ready for Inspection ground rods not properly installed
06/12/2017 ELECTRIC - SERVICE UPGRADE Denied 1- provide 2 ground rods 6' apart
2- provide bonding to gas and water
3- provie 2 point of attachment to bldg