Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
06/13/2017 PLUMBING - GAS PRESSURE TEST Approved CLEAR GAS METER
06/07/2017 PLUMBING - GAS PRESSURE TEST Denied 1- SHALL SECURE ALL PIPING AS PER TABLE 415 (IFGC) 2012
2- GAS PIPING PLAN WAS APPROVED IN ERROR, SHALL RUN 1" PIPING ALL THE WAY TO THE FIRST BRANCH LINE TO THE FURNACE.
3- SHALL PROVIDE A BOND GROUND ON GAS LINE MINIMUM #6 CONDUCTOR.
4- SHALL HARD PIPE THE 1/2" GAS DROP TO THE WATER HEATER THRU THE WATER HEATER ENCLOSURE AND PROVIDE A SEDIMENT TRAP.
5- SHALL PROVIDE A CARBON MONOXCIDE DETECTOR.
6- SHALL PROVIDE A FULL SIZE T & P DRAIN AT THE WATER HEATER.