Permit: T17CM04347

Parcel: 120090710

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
07/07/2017 EXCAVATION/LAYOUT REBAR & ZON Approved
07/06/2017 EXCAVATION/LAYOUT REBAR & ZON Partial Approval BACK ADDITION OK TO POUR. FRONT PORCH IS NOT TO PLAN AND REQUIRES AN EXTERIOR PERIMETER FOOTING OF 10" PER DETAILS. BRICK VENEERS WERE USED FOR CHAIRS AND CONTRACTOR NOTIFIED CODE REQUIRES MASONRY, CONCRETE, OR STEEL CHAIRS, AS TO PREVENT DETERIORATION WITHIN THE SLAB
06/21/2017 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection not per plan