Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T17CM04116
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/19/2017 | MECHANICAL - FINAL | Approved | ||
10/17/2017 | MECHANICAL - FINAL | Denied | duct smoke detector test failed, no unit shutdown, a re-fee is being attached to this permit | |
10/16/2017 | MECHANICAL - FINAL | Not ready for Inspection | duct smoke detector failed test | |
10/12/2017 | MECHANICAL - FINAL | Not ready for Inspection | no duct smoke detector installed pending air balance report |
|
10/12/2017 | MECHANICAL - FINAL | Partial Approval | REVIEW OF AIR BALANCE COMPLETE |