Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/27/2017 | MECHANICAL - INTERMEDIATE | Approved | OK FOR INSULATION AND SHEET ROCK. | |
| 07/20/2017 | MECHANICAL - INTERMEDIATE | Partial Approval | FINISH CONDENSATE DRAIN LINES. SECURE EX. FAN DUCTS TO FAN. TERMINATE THROUGH ROOF. REVISE PLANS TO SHOW ALL MINI SPLIT UNITS. |
|
| 07/19/2017 | MECHANICAL - INTERMEDIATE | Partial Approval | CONDENSATE CANNOT BE REDUCED FROM OUTLET SIZE ON UNIT. 1/2" I.D. DRAIN LINE NOT ADEQUATE. INSTALL EXHAUST FANS. |
|
| 07/10/2017 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | INSTALL A/C DUCTWORK PER PLANS ALONG WITH LINE SETS AND DRAIN FOR MINI SPLIT, AND BATHROOM EXHAUST FANS. |