Permit: T17CM03899

Parcel: 141093510


Addresses:

6526 E BRUSHBACK LP


Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Permit Number - T17CM03899

Inspection Description - PLUMBING - SEWER HCS CONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
06/12/2017 PLUMBING - SEWER HCS CONNECT Approved
06/09/2017 PLUMBING - SEWER HCS CONNECT Denied correct flat spot, compact dirt under pipe in over excavated trench

failure to comply may result in refee
*
06/08/2017 PLUMBING - SEWER HCS CONNECT Denied R2604.1 Bottom of trench shall provide continuous and load bearing support.
Over excavated trenching shall be brought to grade with clean compactible fill
R2605.1 Below ground piping shall be supported on a firm bed for it's entire length.
1.
P2609.2 all materials used shall be installed in strict accord with it's listing
Pipe supports shall be listed for such use and shall not cut or abraid
support sewer

courtesy inspection for Jay
06/07/2017 PLUMBING - SEWER HCS CONNECT Denied support sewer

courtesy inspection for Jay