Permit: T17CM03891

Parcel: 114480350

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
08/29/2017 PLUMBING - INTERMEDIATE Approved
08/24/2017 PLUMBING - INTERMEDIATE Denied 1- SHALL PROVIDE MISSION SPECIALTY COUPLINGS ON ALL CONNECTIONS OF ABS TO CAST IRON NO HUB.
2- SHALL PROVIDE THE REQUIRED SAFTEY NAIL PLATES ON TOP AND SOLE PLATES AND ALSO ON STUD PENETRATIONS.
3- SHALL LOCATE WATER LINES NO CLOSER THAN 12 INCHES FROM CAN LIGHTS.
4- SHALL PROVIDE A DOUBLE FIXTURE FITTING AT DOUBLE LAVATORIES.
5- THE 2 INCH WASTE LINE CAN NOT BE CONNECTED TO THE WATER CLOSET DRY VENT.
6- BRANCH VENTS SHALL BE LOCATED 6 INCHES HORIZONTAL ABOVE THE FLOOD LEVEL RIM OF FIXTURES.
7- SHALL PROVIDE A WATER TEST ON THE DWV SYSTEM TO THE TOP OF VENTS THRU ROOF.
8- SHALL SEAL ALL ELECTRICAL AND PLUMBING PENBETRATIONS THRU THE TOP PLATES WITH FIRE RATED FOAM OR CAULK.