Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2017 | PLUMBING - INTERMEDIATE | Approved | ||
| 08/24/2017 | PLUMBING - INTERMEDIATE | Denied | 1- SHALL PROVIDE MISSION SPECIALTY COUPLINGS ON ALL CONNECTIONS OF ABS TO CAST IRON NO HUB. 2- SHALL PROVIDE THE REQUIRED SAFTEY NAIL PLATES ON TOP AND SOLE PLATES AND ALSO ON STUD PENETRATIONS. 3- SHALL LOCATE WATER LINES NO CLOSER THAN 12 INCHES FROM CAN LIGHTS. 4- SHALL PROVIDE A DOUBLE FIXTURE FITTING AT DOUBLE LAVATORIES. 5- THE 2 INCH WASTE LINE CAN NOT BE CONNECTED TO THE WATER CLOSET DRY VENT. 6- BRANCH VENTS SHALL BE LOCATED 6 INCHES HORIZONTAL ABOVE THE FLOOD LEVEL RIM OF FIXTURES. 7- SHALL PROVIDE A WATER TEST ON THE DWV SYSTEM TO THE TOP OF VENTS THRU ROOF. 8- SHALL SEAL ALL ELECTRICAL AND PLUMBING PENBETRATIONS THRU THE TOP PLATES WITH FIRE RATED FOAM OR CAULK. |