Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T17CM03789
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/21/2019 | PLUMBING - INTERMEDIATE | Approved | ||
| 05/17/2019 | PLUMBING - INTERMEDIATE | Denied | Work not being completed, another failed inspection will result in a reinspection fee. | |
| 05/17/2019 | PLUMBING - INTERMEDIATE | Denied | Work not being completed, another failed inspection will result in a reinspection fee. | |
| 05/15/2019 | PLUMBING - INTERMEDIATE | Denied | Fire stop above ceiling broken or not properly installed or sealed, wiring not properly sealed or nail plated, plumbing not on test, sealed through penetrations, mechanical ducts pinched off, boot box is not properly framed in, condensate vent to be above drain pan, exhaust duct not completed RC channel not to be hung with sheet rock screws, inspections stopped at this time too many items to list, this is not a Complete list. | |
| 05/08/2019 | PLUMBING - INTERMEDIATE | Partial Approval | Second floor. | |
| 05/03/2019 | PLUMBING - INTERMEDIATE | Partial Approval | Third floor. |