Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T17CM03784
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2019 | PLUMBING - ROUGH, SOIL | Approved | roof drain systems | |
| 04/27/2018 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1- ALL CORRECTIONS HAVE BEEN MADE. 2- NOTE; THIS INSPECTION IS FOR THE FIRST FLOOR UNDERGROUNG PLUMBING ONLY. OKAY TOT COVER. |
|
| 04/25/2018 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- SHALL LOCATE THE OUTLET OF THE VENTS FOR THE WATER CLOSETS ABOVE THE CENTER LINE OF THE SOIL LINE. 2- SHALL PROVIDE A MINIMUM DISTANCE OF TWO TIMES THE PIPE SIZE FOR THE MOP SINK TRAP ARM. 3- RETEST THE SYSTEM. * |