Permit: T17CM03783

Parcel: 12101103E

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T17CM03783

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/06/2017 BUILDING - FINAL Approved
07/04/2017 BUILDING - FINAL Partial Approval PROVIDE A TIME CLOCK AT HOOD.
FLEX DUCT NOT ALLOWED FOR TEMPORARY USE AT HOOD.
PROVIDE AIR BALANCE REPORT.