Permit: T17CM03780

Parcel: 14029052C

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
11/16/2018 BUILDING - FINAL Approved REVIEW OF AIR BALANCE REPORT COMPLETED
10/17/2018 BUILDING - FINAL Partial Approval Balance report shows inadequate ventilation of restrooms. Rebalance to provide exhaust rate greater than or equal to the AC air supplied to each restroom. 07/17/2017 PER BOB SHERRY
07/14/2017 BUILDING - FINAL Partial Approval pending all inspactionsand air balance review
07/03/2017 BUILDING - FINAL Partial Approval Roll up door not in

Inspector has no issues preventing TCO