Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2017 | ELECTRIC - SERVICE RELOCATION | Approved | CLEAR ELECTRIC RECN. | |
| 07/12/2017 | ELECTRIC - SERVICE RELOCATION | Denied | 1- SEE COMMENTS FROM 07-10-17 AND MAKE ALL CORRECTIONS PRIOR TO CAQLLING IN A INSPECTION REQUEST TO AVOID A REINSPECTION FEE | |
| 07/10/2017 | ELECTRIC - SERVICE RELOCATION | Denied | 1- SHALL PROVIDE PROTECTION AND PROVIDE THE APPROVE CONNECTOR FOR THE EXISTING CONDUCTOR THAT PENETRATES THE BOTTOM OF THE SERVICE PANEL. 2- SHALL PROVIDE A COVER FOR THE UNUSED OPENING AT THE BOTTOM OF THE SERVICE PANEL. 3- SHALL SECURE THE UFER GROUND. 4- SHALL REPLACE OR FIX THE SERVICE PANEL DOOR. |