Permit: T17CM03522

Parcel: 12710084B


Addresses:

6216 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/30/2017 PLUMBING - FINAL Approved
06/21/2017 PLUMBING - FINAL Denied 1- SEE NOTES FROM PREVIOUS INSPECTION PERFORMED ON 06/15/17
06/15/2017 PLUMBING - FINAL Denied 1- THE APPROVED PLANS CALL FOR A 3" VENT THRU ROOF.
2- SHALL COMPLETE THE DRYER VENT.
3- SHALL PROVIDE A WATER TEST ON THE DWV SYSTEM IN THE PONY WALL.
4- SHALL PROVIDE PROTECTION OF COPPER WATER LINES THAT5 COME IN CONTACT WITH THE DRYER VENT.
5- SHALL PROVIDE A LOCK OUT TAG OUT CLIP ON THE WATER HEATER CIRCUIT BREAKER.