Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
Permit Number - T17CM03522
Inspection Description - PLUMBING - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/30/2017 | PLUMBING - PROGRESS | Approved | ||
06/15/2017 | PLUMBING - PROGRESS | Denied | 1- THE APPROVED PLANS CALL FOR A 3" VENT THRU ROOF. 2- SHALL COMPLETE THE DRYER VENT. 3- SHALL PROVIDE A WATER TEST ON THE DWV SYSTEM IN THE PONY WALL. 4- SHALL PROVIDE PROTECTION OF COPPER WATER LINES THAT5 COME IN CONTACT WITH THE DRYER VENT. 5- SHALL PROVIDE A LOCK OUT TAG OUT CLIP ON THE WATER HEATER CIRCUIT BREAKER. |
|
06/02/2017 | PLUMBING - PROGRESS | Denied | 1- SHALL PROVIDE AN APPROVED PLAN FOR THE ADDED WASHER BOX AND SINK LOCATED IN THE SOUTH WALL. DO NOT COVER. |