Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T17CM03443
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2017 | FIRE - FINAL | Approved | ||
| 12/13/2017 | FIRE - FINAL | Partial Approval | 1) Correct address on front of bldg. 12" numbers need to be posted on front of bldg and on front door which is in the rear. Remove incorrect address numbers. 2) Need knox FDC plug. Show proof you ordered. 3) Locout FACP breaker. 4) Repair or remove exit sign over north exit door. 5) Remove exit sign over door #d107 or change lockset to quarterturn lock. 6) Add sign above FDC with address or suite #'s since it's only serves one suite. |
|
| 11/22/2017 | FIRE - FINAL | Not ready for Inspection | Noted to the General Contractor that Sprinkler system will need to be monitored before C of O is given. |