Permit: T17CM03376

Parcel: 117131560


Addresses:

192 S STONE AV


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T17CM03376

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/24/2019 FIRE - FINAL Approved
04/04/2019 FIRE - FINAL Partial Approval OK FOR TCO
03/25/2019 FIRE - FINAL Partial Approval Tested the emergency and exit lights March 23rd at 5:30 a.m. Found that the 1st floor front entry did not have emergency lights installed
3 lights need to be replaced on the 3rd floor.
2nd floor back east office needs to have the light corrected. EXIT signs need a solid back so that they do not read TIXE

Need to add two-way communication at the elevator landings
Need to test for the ERRC prior to COFO
Stairwells need to have signs showing directions and floors
Need to add the address on the building in 12" letters
Need to add a KNOX Box at each stairwell and the front entry
Provide KNOX FDC Caps and 2 KNOX Elevator Boxes
Stairwell doors are not allowed to be locked per IFC 1008.1.9.11
Need to have all signs FDC, FACP Room, RISER ROOM, ELECTRICAL ROOM, MECHANICAL ROOM SIGNS.
03/23/2019 FIRE - FINAL Partial Approval Tested the emergency and exit lights March 23rd at 5:30 a.m. Found that the 1st floor front entry did not have emergency lights installed
3 lights need to be replaced on the 3rd floor.
2nd floor back east office needs to have the light corrected. EXIT signs need a solid back so that they do not read TIXE

Need to add two-way communication at the elevator landings
Need to test for the ERRC prior to COFO
Stairwells need to have signs showing directions and floors
Need to add the address on the building in 12" letters
Need to add a KNOX Box at each stairwell and the front entry
Provide KNOX FDC Caps and 2 KNOX Elevator Boxes
Stairwell doors are not allowed to be locked per IFC 1008.1.9.11
Need to have all signs FDC, FACP Room, RISER ROOM, ELECTRICAL ROOM, MECHANICAL ROOM SIGNS.