Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/24/2019 | FIRE - ALARM FINAL | Approved | ||
| 03/25/2019 | FIRE - ALARM FINAL | Partial Approval | Fire alarm permit T18FC00688 Simplex Remove the A/V's from stairs, speakers to remain Add a visual to the walk in cooler Swap Visual wih AV in the Bishops office Label all AHU units and test switches Add Spanish as a second language to the FACP program Need a NFPA 72 ROC once the audibility and intelligibilty test is complete |