Permit: T17CM03376

Parcel: 117131560


Addresses:

192 S STONE AV


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T17CM03376

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/24/2019 FIRE - ALARM FINAL Approved
03/25/2019 FIRE - ALARM FINAL Partial Approval Fire alarm permit T18FC00688 Simplex
Remove the A/V's from stairs, speakers to remain
Add a visual to the walk in cooler
Swap Visual wih AV in the Bishops office
Label all AHU units and test switches
Add Spanish as a second language to the FACP program
Need a NFPA 72 ROC once the audibility and intelligibilty test is complete