Permit: T17CM03374

Parcel: 127122650


Addresses:

5721 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T17CM03374

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/14/2017 FIRE - FINAL Approved
12/06/2017 FIRE - FINAL Denied 1) Need sprink final. See sprink notes.
2) Add PRV to riser.
3) Need knox FDC plug.
4) Label riser room door "riser room."
5) Label fire alarm door "FACP."
6) Mount address numbers on top of bldg.
7) Mount extinguishers.
8) Need to test all EM lighting and exit signs.
9) Obtain operational permit for "places of assembly."
10) Keep CO2 quantity at or under 100lbs. Do not install bulk tank.
11) Need as-builts for hood. Added extra nozzles.
12) Mount knox box and provide key.