Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2017 | FIRE - FINAL | Approved | ||
| 12/06/2017 | FIRE - FINAL | Denied | 1) Need sprink final. See sprink notes. 2) Add PRV to riser. 3) Need knox FDC plug. 4) Label riser room door "riser room." 5) Label fire alarm door "FACP." 6) Mount address numbers on top of bldg. 7) Mount extinguishers. 8) Need to test all EM lighting and exit signs. 9) Obtain operational permit for "places of assembly." 10) Keep CO2 quantity at or under 100lbs. Do not install bulk tank. 11) Need as-builts for hood. Added extra nozzles. 12) Mount knox box and provide key. |