Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2017 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 04/26/2017 | PLUMBING - GAS PRESSURE TEST | Denied | 1- CHECK THE SYSTEM FOR LEAKS, THE TEST GAGE DROPPED PRESSURE DURING THE INSPECTION. 2- SHALL PROVIDE APPROVED MATERIALS FOR THE WATER HEATER T & P DRAIN AND TERMINATE IT TO DAYLIGHT AT 6 INCHES ABOVE GRADE. 3- SHALL PROVIDE (3) SHEET METAL SCREWS PER JOINT ON THE WATER HEATER AND FURNACE FLU VENTS AT EACH JOINT AND DRAFT COLLAR. 4- SHALL BOND THE GAS LINE. |