Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/20/2017 FRAMING Approved
07/18/2017 FRAMING Partial Approval ok to insulate

Clothes dryer shall be elevated er code section 1307.3. and Install Instructions; raise dryer vent connection to 18".
Redline all changes on your approved plan including change for mechanical system, condensate, washer and dryer location, and grey water with revision to follow prior to final. Water heater reuires vehicular protection, install bollard;IRC M1307.3.1.
Support line set tubing above ceiling. Safety plate shall extend down 2 inches. Provide code approved supports on copper tube.

Seal floor penetrations.
Address meter base.
Support duct above arch
install bushing at stove outlet box.
protect copper from stucco
07/12/2017 FRAMING Not ready for Inspection protect copper from stucco, seal all floor penetrations, provide top plate repair at int top plate, nail protection shall extend down 2".
Protective bushing at stove recepticle box is not in all the way, note a clamping device is required per code. Support flex ducts. Going forward please start using code approved strapping or clamps for copper tubing, ie lineset.

Provide a city approved plan revision for changes made to garage wall, mech equip, condensate and any other changes. Redline plan for now with changes to follow.

Grey washer not yet installed.