Permit: T17CM03222

Parcel: 140551670

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
07/20/2017 PLUMBING - INTERMEDIATE Approved
07/18/2017 PLUMBING - INTERMEDIATE Not ready for Inspection Clothes dryer shall be elevated er code section 1307.3. and Install Instructions; raise dryer vent connection to 18".
Redline all changes on your approved plan including change for mechanical system, condensate, washer and dryer location, and grey water with revision to follow prior to final. Water heater reuires vehicular protection, install bollard;IRC M1307.3.1.
Support line set tubing above ceiling. Safety plate shall extend down 2 inches. Provide code approved supports on copper tube.
DWV is not under test.
Seal floor penetrations.
Address meter base.
Support duct above arch
install bushing at stove outlet box.
protect copper from stucco