Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2017 | FIRE - FINAL | Approved | ||
| 11/16/2017 | FIRE - FINAL | Partial Approval | 1. Ok for TCO. 2. Mag locks to be tied into Fire Alarm by EY Security. |
|
| 11/14/2017 | FIRE - FINAL | Denied | 1. Elevator smoke curtains not tied into Fire Alarm. 2. Mag locks on egress doors need to release on Fire Alarm. 3. Sprinkler heads need to added in break room next to glass wall. 4. Wall needs to be added to obstruct 2 sprinkler heads in hallway. 5. Fire extinguishers to be added. 6. Circuit 54 needs Red Lockout. 7. Blackout needed on back side of EXIT sign to not read TIXE. 8. Approved Fire Alarm Plans still needed. |