Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T17CM02827
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2017 | MECHANICAL - HOODS | Approved | ||
11/27/2017 | MECHANICAL - HOODS | Partial Approval | 1st layer wrap only | |
11/21/2017 | MECHANICAL - HOODS | Partial Approval | ok to 1st layer wrap | |
11/01/2017 | MECHANICAL - HOODS | Denied | 1- grease duct not to code, all 3 need to be re-done 2- provide written approval from engineer on square to round off-sets |
|
10/26/2017 | MECHANICAL - HOODS | Partial Approval | SMOKE TEST TO 2 OUT OF 3 GREASE DUCTS. OK FOR 1ST WRAP EXCEPT NORTH GREASE DUCT SMOKE TEST FAIL | |
10/24/2017 | MECHANICAL - HOODS | Not ready for Inspection | INSTALL CLEANOUT DOORS FOR TEST |