Permit: T17CM02821

Parcel: 14026040A


Addresses:

2850 E DREXEL RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T17CM02821

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/14/2018 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
05/21/2018 MECHANICAL - ABOVE CEILING Not ready for Inspection provide minimum 2" beaded collars at flex duct connections
duct insulation missing
provide seismic supports at grills
05/18/2018 MECHANICAL - ABOVE CEILING Partial Approval MECH ABOVE CEILING IN SHIPPING ROOM OK TO DROP LID
05/07/2018 MECHANICAL - ABOVE CEILING Not ready for Inspection WORK NOT COMPLETE
05/03/2018 MECHANICAL - ABOVE CEILING Partial Approval FINISH INSULATING DUCT BY N. ENTRANCE. THE REST OF OPERATIONS AREA OK.
05/01/2018 MECHANICAL - ABOVE CEILING Not ready for Inspection see detailed listing on site