Permit: T17CM02460

Parcel: 116300390

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T17CM02460

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/29/2017 PLUMBING - INTERMEDIATE Approved
12/28/2017 PLUMBING - INTERMEDIATE Denied 1 shim bearing headers 2 install diamond mesh on horizontal surfaces greater than 12" 3 pancake boxes at garage overfilled 4 ground metal box atbreakfast nook 5 bond spa motor 6 provide min 12" from can light to pex in bath 3 7 trap arm in laundry overlength 8 provide gas gauge with 1/10th pound increments 9 provide insulation shield on fireplace vent
12/13/2017 PLUMBING - INTERMEDIATE Denied SECURE 90 VENTS THRU ROOF
SECURE CLOSET FLANGE
NAIL PROTECT THROUGHOUT
12/06/2017 PLUMBING - INTERMEDIATE Partial Approval FIRE FOAM ALL TOP PLATE PENETRATIONS
STUB OUT FUTURE SOLAR AT WATER HEATER
BOND GAS LINE
SECURE LINE SETS VERTICAL IN WALLS
SECURE 90 VENTS THRU ROOF
EXCEPT JACUZZI TUB
PROVIDE 12" CLEARANCE PEX FROM CANS
11/28/2017 PLUMBING - INTERMEDIATE Not ready for Inspection LATHE PRIOR