Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T17CM02453
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/12/2019 | PLUMBING - INTERMEDIATE | Approved | ||
| 11/06/2019 | PLUMBING - INTERMEDIATE | Partial Approval | Pex required to be 12" from lighting fixtures and 18" from sweat joint. Remove dryer gas line or update drawings. Secure toilet flanges. |