Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T17CM02369

Parcel: 13348128F


Addresses:

100 S HOUGHTON RD


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T17CM02369

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/17/2019 FIRE - FINAL Approved REMINDER: 5 ANSUL SYSTEMS ARE NOT CONNECTED TO THE FIRE ALARM PER HARVEY BROWN AT TFD
05/14/2019 FIRE - FINAL Partial Approval These are notes only. May still need to complete other items. Small self contained appliances (popcorn machines and fryers) were approved without hoods and not required to be interconnected to alarm panel.
04/30/2019 FIRE - FINAL Partial Approval Fire alarm system did not pass the audibility intelligibility test. Need to adjust the speaker strobe watts and or add more devices.
The new added exit signs have chevrons that are not needed and they are all white with a light green and do meet the intent of the code. Need to move/replace exit signs
Will look into new fryer's installed in the kitchen to make sure that they are UL710B.
04/15/2019 FIRE - FINAL Partial Approval NOT READY -
Need to pay early morning inspection fees.
Need exit lights every 100" Emergency and exit lights shall be 11 Lux or 1 Candella through all exit passageways including the employee corridor and the mezanine
Make sure that the fire alarm contractor and electrician are onsite for final next time. Pay reinspection fees as well
10/17/2018 FIRE - FINAL Partial Approval OK FOR TCO
1) Need emergency & exit lights every 100'. Emergency lights to be 11 lux or 1 candella. All egress paths to be illuminated properly.
2) Move the fire sprinkler bell from the south wall to the west wall
3) Shut down the music system in the hallway, lobby and bathrooms
4) Needs address front 15" letter and on all back doors
5) Needs the following signs: Fire Riser Room, F.D.C., Not a Door, Employees only
6) Employee passageway west needs emergency and exit lights
7) Need drawings and permit for the CO2 system
8) Weld/remove back door
9) All exterior doors need to have emergency lights
10) Mezanine needs emergency and exit lights
11) Mezzanine move the light and or adjust the fire sprinkler head over middle projector
12) Obtain a places of assembly permit from TFD