Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T17CM02369
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/17/2019 | FIRE - ALARM FINAL | Approved | REMINDER: 5 ANSUL SYSTEMS ARE NOT CONNECTED TO THE FIRE ALARM PER HARVEY BROWN AT TFD | |
04/30/2019 | FIRE - ALARM FINAL | Partial Approval | Fire alarm system did not pass the audibility intelligibility test. Need to adjust the speaker strobe watts and or add more devices. | |
04/15/2019 | FIRE - ALARM FINAL | Partial Approval | Need to correct the duct smoke detector that is now in trouble on the FACP. FACP needs to be clear for fire alarm final. Need to shut down the music system loctaed in the front lobby, back hall and bathrooms Need to perform the A & I test for fire alarm final approval |
|
10/18/2018 | FIRE - ALARM FINAL | Partial Approval | Need to replace low notification devices Needs RED Lock on the Breaker Need to perform the A&I test for the fire alarm Replace the glass front with a dead front |