Permit: T17CM02358

Parcel: 138042390


Addresses:

718 W CALLE MEDINA

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
11/04/2019 PLUMBING - INTERMEDIATE Approved
10/24/2019 PLUMBING - INTERMEDIATE Denied 1- Shower and water closet vents shall rise vertically of trap arms.
2- Shall provide a water test on the DWV system.
07/06/2018 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999
1- SHALL PROVIDE AND VENT WITH A TRAP ARM FOR THE SHOWER DRAIN.
2- WATER CLOSET VENT SHALL BE LOCATED ABOVE THE CENTER LINE OF THE DRAIN OR PLUMB A CONVENTIONAL METHOD.
3- SHALL PROVIDE A WATER TEST ON THE SYSTEM ALL THE WAY UP TO VENT THRU ROOF.


*
03/16/2018 PLUMBING - INTERMEDIATE Denied provide access for inspectin