Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T17CM02234

Parcel: 133501760


Addresses:

731 N PROMONTORY DR


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T17CM02234

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/24/2017 PLUMBING - INTERMEDIATE Approved
03/22/2017 PLUMBING - INTERMEDIATE Denied 1- WATER SUPPLY IS UNDERSIZED AT THE 1" SUPPLY AT THE GARAGE AND IN THE BATROOM PLUMBING WALLS. NO MORE THAT TWO FIXTURES CAN BE SUPPLIED ON A 1/2" WATER LINE.
2- ZIP TIES ARE NOT ACCECPTED FOR STRAPPING THE WATER HEATER WATER SUPPLIES.
3- SHALL RUN A MINIMUM OF 1" TO THE WATER HEATER SUPPLY AND 3/4" MINIMUM TO THE BATHROOM PLUMBING WALLS.
4- KITCHEN WALL IS OKAY TO SHEET ROCK AND REINSTALL THE CABINETS.