Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T17CM02234
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/24/2017 | PLUMBING - INTERMEDIATE | Approved | ||
03/22/2017 | PLUMBING - INTERMEDIATE | Denied | 1- WATER SUPPLY IS UNDERSIZED AT THE 1" SUPPLY AT THE GARAGE AND IN THE BATROOM PLUMBING WALLS. NO MORE THAT TWO FIXTURES CAN BE SUPPLIED ON A 1/2" WATER LINE. 2- ZIP TIES ARE NOT ACCECPTED FOR STRAPPING THE WATER HEATER WATER SUPPLIES. 3- SHALL RUN A MINIMUM OF 1" TO THE WATER HEATER SUPPLY AND 3/4" MINIMUM TO THE BATHROOM PLUMBING WALLS. 4- KITCHEN WALL IS OKAY TO SHEET ROCK AND REINSTALL THE CABINETS. |