Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T17CM02233
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/30/2017 | PLUMBING - GAS PRESSURE TEST | Approved | ||
03/28/2017 | PLUMBING - GAS PRESSURE TEST | Denied | 1. LOSES PRESSURE WITHIN 15 MINUTES. WATER HEATER IS NOT PROPERLT INSTALLED, MISSING COMBUSTION VENT ON TOP ON HEATER. MISSING T/P RELIEF VALVE PIPE MISSING SEDIMENT TRAP VENT NEEDS TO BE DOUBLE WALL B-VENT OUTSIDE OF CABINET |
|
03/24/2017 | PLUMBING - GAS PRESSURE TEST | Denied | PRESSURE TEST FAILED AGAIN, REPAIR LEAKS BEFORE RE-CALLING THIS INSPECTION. | |
03/23/2017 | PLUMBING - GAS PRESSURE TEST | Denied | 1 PRESSURE TEST FAILED 2 GAUGE NEEDS TO BE A 15 PSI MAX ANOTHER FAILED INSPECTION WILL RESULT IN A RE-FEE |
|
03/22/2017 | PLUMBING - GAS PRESSURE TEST | Denied | PRESSURE TEST FAILED. REPAIR AND RE-CALL INSPECTIONS. |