Permit: T17CM02230

Parcel: 11103206A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T17CM02230

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/03/2017 PLUMBING - FINAL Approved
03/29/2017 PLUMBING - FINAL Denied 1- SHALL PROVIDE GAS BOND AS REQUESTED FROM PREVIOUS INSPECTION. SEE NOTE #1.
2- SHALL SEAL THE GAS LINE PENETRATION THRU THE EXTERIOR WALL.
03/27/2017 PLUMBING - FINAL Denied 1- SHALL PROVIDE GAS BOND THAT IS CONNECTED TO THE ELECTRICAL GROUNDING SYSTEM.
2- SHALL EXTEND THE FURNACE FLU VENT AND TERMINATE A MINIMUM OF 3'-0" ABOVE THE COOLER WHEN THE B-VENT IS LOCATED WITHIN 10' RADIUS.
3- CHECK THE GAS LINE SYSTEM FOR LEAKS.