Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T17CM02082
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/26/2017 | ELECTRIC - FINAL | Approved | APPROVED. SKYPE. DGC | |
04/27/2017 | ELECTRIC - FINAL | Partial Approval | MAIN BREAKER DE-RATE FROM 125 TO 100 IS REQUIRED PER PLAN. ADD PERMANENT ADDRESS LABEL TO MAIN PANEL AT TIME OF DE-RATE. RE-CALL ALL INSPECTIONS WHEN DE-RATE IS COMPLETED. OK TO CLEAR DGC |