Permit: T17CM01930

Parcel: 205945870

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T17CM01930

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/13/2017 BUILDING - FINAL Approved
06/12/2017 BUILDING - FINAL Not ready for Inspection
06/09/2017 BUILDING - FINAL Denied ABS glue may not be used on PVC. Pvc Primer and Solvent cement shall be used.
Install Co Adaptor on upstream(house side) of "two way co".
Correct slope on TPR drain.
Remove tape from joints of vent connectors.
Install lead roof jacks properly.
Level Condensing unit.
Install tube clamp on Dw pumped discharge hose. Bread bag tie is not acceptible.
Dope may not be used on AAV
06/08/2017 BUILDING - FINAL Not ready for Inspection ok for gasclr