Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2017 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/01/2017 | PLUMBING - FINAL | Denied | GRAB BAR NOT SECURED GFCI IN KITCHEN AND ROOF TOP MISSING 1ST FLOOR ADA TOILET TO FAR FROM WALL 2ND FLOOR RESR ROOMS NOTCOMPLETE |
|
| 08/31/2017 | PLUMBING - FINAL | Partial Approval | PROVIDE 1/8" PER FT. SLOPE AT CONDENSATE. FINISH INSTALLING PLUMBING FIXTURES. ANY RECEPTACLE WITHIN 6' OF A SINK TO BE GFI. INSULATE ADA LAV. DRAINS. FINISH ALL ELEC. WORK. LIST NOT COMPLETE. |
|
| 08/30/2017 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/29/2017 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |