Permit: T17CM01820

Parcel: 11451216G

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/10/2017 PLUMBING - FINAL Approved 1- BLDG. FINAL IS OKAY FOR C. OF O. PENDING FIRE APPROVAL.
04/06/2017 PLUMBING - FINAL Denied 1- SHALL PROVIDE AN OPEN FRONT SEAT FOR THE WATER CLOSET.
2- SHALL PROVIDE A TEMPERING VALVE AS PER PLAN FOR THE LAVATORY.
3- SHALL LOCATE THE WATER CLOSET 16" TO 18" TO THE CENTER OF WATER CLOSET FOR SIDE WALL CLEARANCE.
4- SHALL LOCATE THE TOP OF THE FLOOD RIM LEVEL OF LAVATORY 34" A.F.F MAX.
5- SHALL LOCATE THE TOILET PAPER DISPECSER MIN. 24" FROM THE REAR WALL.
6- SHALL PROVIDE AN EXPANSION TANK AT THE WATER HEATER.
7- SHALL PROVIDE THE REQUIRED SIGNAGE FOR THE TOILET ROOM AS PER ICC A117.1- 2009.
8- SHALL PROVIDE A ACCESIBLE DOOR HANDLE ON THE TOILET ROOM DOOR.
9- SHALL LOCATE THE GRAB BARS MAX 36" A.F.F. TO THE TOP OF GRAB BARS