Permit: T17CM01820

Parcel: 11451216G

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
04/10/2017 PLUMBING - ROUGH, SOIL Approved 1- BLDG. FINAL IS OKAY FOR C. OF O. PENDING FIRE APPROVAL.
03/23/2017 PLUMBING - ROUGH, SOIL Denied 1- SHALL PROVIDE A WATER TEST ON THE DWV SYSTEM TO TOP OF VTR.
2-SHALL PROVIDE AN APPROVED METHOD OF STRAPPING ON ALL DOMESTIC WATER DROPS IN WALLS. P-TAPE IS NOT LISTED OR APPROVED MATERIAL.
3- THE MAXIMUM TRAP ARM DISTANCE FOR THE 2" TRAP ARM FOR THE BODY WAX SINK IS 8'-0".