Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2017 | FRAMING | Approved | ||
| 07/20/2017 | FRAMING | Not ready for Inspection | 1- trusses bearing at non bearing points 2- H-2.5 not properly installed through out 3- provide engineers truss report |
|
| 07/06/2017 | FRAMING | Denied | CHARRED TRUSSES AND FRAMING MEMBERS WITHIN THE STRUCTURE. PROVIDE AN ENGINEERS LETTER VERIFYING MEMBERS ARE NOT COMPROMISED OR REPLACE THEM. SEAL TOP PLATE AT FURRED OUT WALL FOR FIRE BLOCKING. ADD BLOCKING UNDER TRUSS AT BACK SCREEN DOOR HEADER TO COMPLETE THE CORRECT LOAD TRANSFER TO THE EARTH BELOW. | |
| 07/03/2017 | FRAMING | Not ready for Inspection | LATHE PRIOR |