Permit: T17CM01771

Parcel: 11005314J

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T17CM01771

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/30/2017 FIRE - FINAL Approved separate NOV issued for some outstanding items.
06/29/2017 FIRE - FINAL Denied 1) Submit plans/drawing for hood. Requires separate permit.
2) Obtain operational permit for "places of assembly"
3) Keep CO2 amounts under 101lbs.
4) Remove door decals over door #4.
5) Add panic hardware over door #45
6) Mount extinguishers.
7) Need annual sprinkler and 5yr check valve inspection reports.
8) Need annual fire sprink monitoring alarm report. Could not locate panel.
9) Lack of sprinkler coverage under bar and entrance to bar.
10) Need to verify that hood is interconnceted with monitoring panel.