Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2017 | FIRE - FINAL | Approved | separate NOV issued for some outstanding items. | |
| 06/29/2017 | FIRE - FINAL | Denied | 1) Submit plans/drawing for hood. Requires separate permit. 2) Obtain operational permit for "places of assembly" 3) Keep CO2 amounts under 101lbs. 4) Remove door decals over door #4. 5) Add panic hardware over door #45 6) Mount extinguishers. 7) Need annual sprinkler and 5yr check valve inspection reports. 8) Need annual fire sprink monitoring alarm report. Could not locate panel. 9) Lack of sprinkler coverage under bar and entrance to bar. 10) Need to verify that hood is interconnceted with monitoring panel. |