Permit: T17CM01477

Parcel: 120076950


Addresses:

431 W LINCOLN ST

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
03/29/2017 MECHANICAL - INTERMEDIATE Approved
02/24/2017 MECHANICAL - INTERMEDIATE Denied 1- provide bushing at disconnect
2- whitewire not to be used as a hot leg
3- T-stat wire to be protectd from U.V. damage
4- conduit to be blocked up a minimum of 1.5 inches
5- all roof top duct to have a minimum of R-8 isulation (2 inch)
6- provide P-trap at condensate drain
7- PVC pipe to be coated for U.V. protection
8- condensate pipe to be strapped to wall
9- service outlet required on roof within 25' of unit (110v)
10- all roof penetrations require roof jacks
11- PVC piping to be supported not more than 48" horiz.
12- breaker is over rated for this unit
13- provide proper fitting at top of panel, myers hub or equal