Permit: T17CM01387

Parcel: 116124370

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/21/2017 ELECTRIC - INTERMEDIATE Approved
04/19/2017 ELECTRIC - INTERMEDIATE Denied SECURE ALL BLUE ELECTRICAL BOXES TO FRAMWORK
SECURE ALLL GOUND WIRES TO GROUND SCREWS
MOUNT SUB-PANEL FOR UNIT 4
INSTALL EXTENSION FOR RECESSED BOXES
METAL BOXES REQUIRE ROMEX CONNECTORS
INCORRECT BOXES FOR CEILING FANS
PROTECT WIRING 1 1/4 INCH FROM THE EDGE OF FIRING STRIP.
04/17/2017 ELECTRIC - INTERMEDIATE Not ready for Inspection
03/30/2017 ELECTRIC - INTERMEDIATE Partial Approval PLB / ELECT IN LAUNDRY OK TO COVER