Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2017 | FIRE - FINAL | Approved | ||
| 12/11/2017 | FIRE - FINAL | Partial Approval | Hood #3 temperature probe not working | |
| 12/08/2017 | FIRE - FINAL | Partial Approval | Only needs a hood final. Following notes from last hood inspection: 1) Checked all nozzles and heights. 2) Hood #3 temp probe not working. 3) Need full trip test, again, pull and link. 4) Hood #2 not getting any agent/air when hoods are tripped. Hood #2 is not connected. |
|
| 12/06/2017 | FIRE - FINAL | Partial Approval | -Still need sprinkler final. -Still need hood final. -Finish step for second exit. Located off patio. -Fire bell not working. -Add "riser room" to door. -Need as builts for hoods with proper appliances and cook lineup. -Add nozzle over range, hood #1. Needs two nozzles. -Add nozzles over single ranges "stock pot burners" x 4 or prove they do not need coverage. |
|
| 12/01/2017 | FIRE - FINAL | Denied | -Still need sprinkler final. -Still need hood final. -Add/mount address numbers. 12" on east side and 15" on south side. -Obtain operational permit for "places of assembly." -Correct sprinkler issues. Two areas have obstructions by duct. See sprink notes. Discussed with Navarrette and Mike from MW morrissey. -Finish step for second exit. Located off patio. -Fire bell not working. -Add "riser room" to door. -Need as builts for hoods with proper appliances and cook lineup. -Add nozzle over range, hood #1. Needs two nozzles. -Add nozzles over single ranges "stock pot burners" x 4 or prove they do not need coverage. |