Permit: T17CM01355

Parcel: 141185920


Addresses:

10275 E OLD VAIL RD

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
12/15/2017 FIRE - FINAL Approved
12/11/2017 FIRE - FINAL Partial Approval Hood #3 temperature probe not working
12/08/2017 FIRE - FINAL Partial Approval Only needs a hood final. Following notes from last hood inspection:
1) Checked all nozzles and heights.
2) Hood #3 temp probe not working.
3) Need full trip test, again, pull and link.
4) Hood #2 not getting any agent/air when hoods are tripped. Hood #2 is not connected.
12/06/2017 FIRE - FINAL Partial Approval -Still need sprinkler final.
-Still need hood final.
-Finish step for second exit. Located off patio.
-Fire bell not working.
-Add "riser room" to door.
-Need as builts for hoods with proper appliances and cook lineup.
-Add nozzle over range, hood #1. Needs two nozzles.
-Add nozzles over single ranges "stock pot burners" x 4 or prove they do not need coverage.
12/01/2017 FIRE - FINAL Denied -Still need sprinkler final.
-Still need hood final.
-Add/mount address numbers. 12" on east side and 15" on south side.
-Obtain operational permit for "places of assembly."
-Correct sprinkler issues. Two areas have obstructions by duct. See sprink notes. Discussed with Navarrette and Mike from MW morrissey.
-Finish step for second exit. Located off patio.
-Fire bell not working.
-Add "riser room" to door.
-Need as builts for hoods with proper appliances and cook lineup.
-Add nozzle over range, hood #1. Needs two nozzles.
-Add nozzles over single ranges "stock pot burners" x 4 or prove they do not need coverage.