Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T17CM01002

Parcel: 11460019C

Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Date Description Inspector Results Comments
02/24/2017 PLUMBING - ABOVE CEILING Approved IVRS - Inspection :*
02/21/2017 PLUMBING - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999
1- DOOR WAS LOCKED. SHALL PROVIDE ACCESS AT THE TIME OF INSPECTION REQUEST.


*
02/14/2017 PLUMBING - ABOVE CEILING Denied 1- SHALL PROVIDE MISSION SPECIALTY COUPLING WHEN CONNECTION ABS MATERIAL TO CAST IRON.
2-SHALL PROVIDE BLIND CAPS FOR THE EXISTING FIGURE FIVE FITTING.
3- OKAY TO BACKFILL TRENCH IN THE RESTROOM.
4 SHALL PROVIDE A HANGER EVERY 4'-0" ON HORIZONTAL VENT ABOVE CEILING.
02/14/2017 PLUMBING - ABOVE CEILING Denied