Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/30/2018 |
MECHANICAL - FINAL |
|
Approved |
identify unit data plate. Unit over fused Max fuse size appears to be 40 amp a 50 amp breaker is currently installed. |
| 11/26/2018 |
MECHANICAL - FINAL |
|
Denied |
1- No access to the roof |