Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T17CM00359
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/21/2017 | FIRE - ALARM FINAL | Approved | ||
11/07/2017 | FIRE - ALARM FINAL | Partial Approval | 1. Faulty tamper switch needs to be replaced. 2. Will need to test Alarm with Projectors, Screens and Sound functioning in new and existing theaters. 3. TCO portion of Fire Final passed Fire Alarm Inspection for occupancy. 4. All Duct Detectors passed. |
|
11/03/2017 | FIRE - ALARM FINAL | Cancelled | did not schedule accordingly. did not schedule an appointment with an inspector. i was not able to provide an inspection before 10am. need to reschedule. | |
11/02/2017 | FIRE - ALARM FINAL | Not ready for Inspection | 1. Couldn't get supervisory tamper to reset from Alarm Panel. Need to troubleshoot prior to Fire Alarm Inspection. |