Permit: T17CM00359

Parcel: 110113620

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T17CM00359

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
12/05/2017 MECHANICAL - HOODS Approved
11/28/2017 MECHANICAL - HOODS Not ready for Inspection
11/21/2017 MECHANICAL - HOODS Partial Approval FIRST LAYER OF WRAP OK TO COVER.
11/20/2017 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
11/17/2017 MECHANICAL - HOODS Denied IVRS - Inspection :
See detailed listing on site.| 999


*
11/13/2017 MECHANICAL - HOODS Partial Approval #2 HOOD DUCT - 16' - SMOKE AND DOUBLE WRAP OK TO DROP IN.
10/17/2017 MECHANICAL - HOODS Partial Approval PONY WALLS OK FOR SHEET ROCK.
SMOKE TESTED FINAL CONNECTIONS OF GREASE DUCT.
1ST LAYER OF FIRE WRAP IS OK. OK FOR 2ND LAYER.
10/16/2017 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
10/02/2017 MECHANICAL - HOODS Partial Approval SMOKE TESTED 3 GREASE DUCTS. OK TO DOUBLE WRAP AND INSTALL.
OK FOR CEILING TILES THEATER 7,8, AND 9.
09/29/2017 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
09/06/2017 MECHANICAL - HOODS Partial Approval 1- TYPE 1 GREASE HOOD EXHAUST DUCT SMOKE TEST PROVIDED ON 16 FEET OF EXHAUST DUCT.
2- OKAY FOR DOUBLE WRAP.