Permit: T17CM00318

Parcel: 133281190


Addresses:

8421 E 5TH ST

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
01/26/2017 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
01/25/2017 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999
1- SHALL LOCATE THE OUTLET OF THE VENT ABOVE THE CENTER LINE OF THE DRAIN FOR THE SHOWER.
2- SHALL REMOVE THE SAN TEE THAT IS POSITIONED ON IT'S BACK FOR THE WATER CLOSET AND THEN POSITION THE SAN TEE IN A VERTICAL POSITION AND THEN THE TRAP ARM AND SWEEP FOR THE CLOSET BENT.
3- RE TEST THE SYSTEM.
4- NOTE: OKAY TO BACKFILL THE BLDG. SEWER AND YARD WATER LINE.


*