Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2017 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/13/2017 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | 1-2 ground rods required 2-riser to be minimum 2" diameter 3-minimum wire size for 20 amp breaker is #12 4-provide boing to gas and water 5-consult licensed electrical contractor for corrections 6-ground rod conductorto be minimum #4 |