Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T16OT00907

Parcel: 12215250A

Inspection Status: Partial Approval

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
08/16/2016 FIRE - FINAL Partial Approval The current installed Fire Alarm System is not functioning. The system needs to be serviced or replaced. An existing permit or approved plans were not found and the system needs to be evaluated to determine if it is designed as a Manual Fire Alarm System for the area served.

The occupant load of the building housing classrooms # 1,2,3 and 5 is 118, The occupant load of the building housing classrooms # 6,7,8,9,10,11,12 and 13 is 274. These classrooms are used M - F for a private school K-12 and therefor fall under the occupancy class of E, as it is a private school that has leased the church's buildings for occupation and operations. Because each classroom has at least one exit directly to the outside, it falls out of the code requirements for a sprinkler system, however this school does require an APPROVED fire alarm system.
Fire watch is currently being provided for up to 30 days while it is being determined if it is an approved manual fire alarm system that needs to be serviced or if it needs to be replaced.
08/01/2016 FIRE - FINAL Not ready for Inspection PROPERTY NEEDS TO BE RESEARCHED AS TO OLDER C OF O'S, CURRENT USE, STUDENT NUMBER, SQUARE FOOTAGE. NO WORK DONE, JUST BRINGING A SCHOOL BACK INTO EXISTING ROOMS THAT WERE ONCE USED FOR PRIVATE SCHOOLING ON THE CHURCH PROPERTY.